NOVUS AUTOMATION 1/5
N1500G
UNIVERSAL INDICATOR - OPERATING MANUAL
1. PRESENTATION
N1500G is a universal process indicator which accepts a large
variety of input signals and sensors.
A five-digit LED display shows measured value and all programming
parameters.
Instrument configuration is achieved from the keyboard, without any
hardware change.
The user should read this manual thoroughly before using the
instrument. It is a fine electronic device and should be used
accordingly for best results.
Some of the features of the basic version are:
Universal input: Pt100, thermocouples, 4-20 mA, 0-50 mV and 0-5
Vdc
24Vdc power supply for remote transmitters excitation
Maximum and minimum memory
Digital input with Hold Peak Tare and hold function
Process Variable retransmission in 0-20 mA or 4-20 mA
RS485 MODBUS RTU serial communication
Display: Shows process variable (PV) and the programming
prompts.
ALM1 and ALM2: show alarm status.
INDEX key - This key is used to access the programming
menu and prompts.
BACK key - This key is used to go back to the previously
reached prompt in the menu cycle.
UP / MAX key and
DOWN / MIN - Used to increase
and decrease parameters values, these keys are also used
to display maximum and minimum values stored in memory..
Special FUNCTION key - This special function key is used
for pre-programmed functions as explained in the SPECIAL
FUNCTION KEY section of this manual.
2. PROCESS VARIABLE INPUT - PV
The Process Variable input type should be keyboard programmed by
the user according to the codes shown on table 1 (refer to INPUT
TYPE parameter "in.typ
in.typin.typ
in.typ").
All input types are factory calibrated and no additional calibration is
required.
Thermocouples are calibrated to NBS standards. RTD’s are
calibrated to DIN 43760 (α=0.00385).
TIPO CODE CARACTERÍSTICAS
J
Range: -50 to 760 °C (-58 to 1400 °F)
K
Range: -90 to 1370 °C (-130 to 2498 °F)
T
Range: -100 to 400 °C (-148 to 752 °F)
E
Range: -35 to 720 °C (-31 to 1328 °F)
N
Range: -90 to 1300 °C (-130 to 2372 °F)
R
Range: 0 to 1760 °C (-32 to 3200 °F)
S
Range: 0 to 1760 °C (-32 to 3200 °F)
B
Range: 150 to 1820 °C (302 to 3308 °F)
Pt100
Range: -199.9 to 530.0 °C (-327.8 to 986.0 °F)
Pt100
Range: -200 to 530 °C (-328 to 986 °F)
4-20 mA
Linearizes J. Adjustable range: -110 to 760 °C
4-20 mA
Linearizes K. Adjustable range.: -150 to 1370 °C
4-20 mA
Linearizes T. Adjustable range.: -160 to 400 °C
4-20 mA
Linearizes E. Adjustable range.: -90 to 720 °C
4-20 mA
Linearizes N. Adjustable range -150 to 1300 °C
4-20 mA
Linearizes R. Adjustable range 0 to 1760 °C
4-20 mA
Linearizes S. Adjustable range.: 0 to 1760 °C
4-20 mA
Linearizes B. Adjustable range.: 100 to 1820 °C
4-20 mA
Linearizes Pt100. Adj. range.:-200.0 to 530.0 °C
4-20 mA
Linearizes Pt100. Adj. range.: -200 to 530 °C
0 -50 mV
Linear. Adjustable range.: -1999 to 9999
4-20 mA
Linear. Adjustable range.: -1999 to 9999
0 a 5 V
Linear. Adjustable range.: -1999 to 9999
Table 1 - Input type codes
3. ALARMS
The indicator features 2 alarm outputs in the basic version. Each
alarm has a corresponding LED anunciator in the front panel to show
alarm status.
TYPE PROMPT ACTION
Disabled
off
Alarm is inactive
Sensor Break
(input Error)
ierr
Alarm will go ON if sensor breaks, input
signal is out of range or Pt100 is shorted.
Low Alarm
Lo
Alarm SP
PV
High Alarm
Ki
Alarm SP
PV
Diferential Low
Dif.lo
PV
AL SP + Deviation
AL SP
Diferential High
Dif.ki
PV
Deviation
AL SP
Diferential
Dif
PV
Deviation
Deviation
AL SP
AL SP -
Deviation
PV
AL SP
-
Deviation
Negative Deviation
AL SP
AL SP + Deviat.
Table 2 - Alarm functions
3.1. ALARM FUNCTIONS
The alarms can set to operate in six different functions: Sensor
break, Low Alarm, High Alarm, Differential Low, Differential High or
Differential (Band). These functions are shown in table 2 and
described as follows
3.1.1. Sensor break
The alarm will go ON whenever the sensor breaks or is badly
connected.
3.1.2. Low alarm
The alarm relay will go ON whenever the measured value is below
the alarm set point.
Page view 0
1 2 3 4 5

Summary of Contents

Page 1 - NOVUS AUTOMATION 1/5

NOVUS AUTOMATION 1/5 N1500G UNIVERSAL INDICATOR - OPERATING MANUAL 1. PRESENTATION N1500G is a universal process indicator which accepts

Page 2 - 5. INSTALLATION

Indicator N1500G NOVUS AUTOMATION 2/5 3.1.3. High alarm The alarm relay will be ON whenever the measured value is above the alarm set point. 3.1.4.

Page 3 - TELA PARAMETER DESCRIPTION

Indicator N1500G NOVUS AUTOMATION 3/5 5.2. ELECTRICAL CONNECTIONS The internal electronics can be removed from the front panel without any cable disa

Page 4 - NOVUS AUTOMATION 4/5

Indicator N1500G NOVUS AUTOMATION 4/5 Al1t1 Al1t2 Al2t1 Al2t2 Al3t1 Al3t2 Al4t1 Al4t2 Time Alarms The user can set delayed or sequential alarm

Page 5 - 12. WARRANTY

Indicator N1500G NOVUS AUTOMATION 5/5 Dois parâmetros devem ser configurados para utilização da interface de comunicação serial: o Baud-Rate de