Novus N322RHT User Manual Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
Ac2
Ac2Ac2
Ac2
Action 2 - Control OUTPUT 2 action or Alarm functions:
0
00
0 Reverse control action (heating or humidification). (See (nt
(nt(nt
(nt
parameter below).
1
11
1 Direct control action (cooling or dehumidification).
2
22
2 Low (minimum value) alarm.
3
33
3 High (maximum value) alarm.
4
44
4 Alarm inside the range
5
55
5 Alarm outside the range.
6
66
6 Low alarm with initial blocking.
7
77
7 High alarm with initial blocking.
8
88
8 Inside the range alarm with initial blocking.
9
99
9 Outside the range alarm with initial blocking.
The section Working with the RHT Controller describes how these
functions work.
(nt
(nt(nt
(nt
Assigns the relay for each variable:
0
00
0 OUTPUT 1 = RH; OUTPUT 2 = RH;
1
11
1 OUTPUT 1 = RH; OUTPUT 2 = Temperature;
2
22
2 OUTPUT 1 = Temperature; OUTPUT 2 = RH;
3
33
3 OUTPUT 1 = Temperature; OUTPUT 2 = Temperature;
of1
of1of1
of1
Off time 1 - Defines the minimum off time for control OUTPUT 1. Once
OUTPUT 1 is turned off, it remains so for at least the time programmed in
of1
of1of1
of1. For thermocouple inputs this parameter is not available. This
parameter is intended for refrigeration systems where longer compressor life
is desired. For heating systems, program of1
of1 of1
of1 to zero. Value in seconds, 0
to 999 s.
on1
on1on1
on1
On time 1 - Defines the minimum on time for control OUTPUT 1. Once
turned on, OUTPUT 1 remains so for at least the time programmed in on1
on1on1
on1.
For thermocouple inputs this parameter is not available. This parameter is
intended for refrigeration systems where increased compressor life is
desired. For heating systems, program on1
on1 on1
on1 to zero. Value in seconds, 0 to
999 s.
dl1
dl1dl1
dl1
Delay 1 - Delay time to start control. Upon power-on, control OUTPUT 1 is kept
off until the time programmed in dl1
dl1dl1
dl1 is elapsed. Its usage is intended to
prevent multiple compressors to start simultaneously after the turn-on of a
system with several instruments. Value in seconds, 0 to 250 s.
of2
of2of2
of2
Off time 2 - Defines the minimum off time for control OUTPUT 2. Once
OUTPUT 2 is turned off, it remains so for at least the time programmed in
of2
of2of2
of2. For thermocouple inputs this parameter is not available. This
parameter is intended for refrigeration systems where increased compressor
life is an issue. For heating systems, program on2
on2 on2
on2 to zero. Value in
seconds, 0 to 999 s.
on2
on2on2
on2
On time 2 - Defines the minimum on time for control OUTPUT 2. Once
turned on, OUTPUT 2 remains so for at least the time programmed in on2
on2on2
on2.
For thermocouple inputs this parameter is not available. This parameter is
intended for refrigeration systems where increased compressor life is
desired. Value in seconds, 0 to 999 s. For heating systems, program of2
of2 of2
of2 to
zero.
dl2
dl2dl2
dl2
Delay 2 - Delay time for OUTPUT 2 to turn on relative to OUTPUT 1. This
parameter defines a particular working mode, typically used in multiple stage
systems, where OUTPUT 2 is allowed to go on only if OUTPUT 1 is already
on for at least dL2
dL2dL2
dL2 seconds. Also, OUTPUT 2 is driven off whenever
OUTPUT 1 goes off. dL2
dL2dL2
dL2= 0
0 0
0 disables this function. Value in seconds, 0 to
250 s.
Add
AddAdd
Add
Adress The parameter Add
Add Add
Add is presented in instruments loaded with the
optional RS485 Modbus RTU communication interface.
Set a unique Modbus address for each equipment connected to the network.
Address range is from 1 to 247.
Level 3 – Calibration level
The N322RHT is factory calibrated. The following parameters should be accessed only by
experienced personnel. To enter this cycle, the key must be kept pressed for 4 seconds.
Don’t press the and keys if you are not sure of the calibration procedures.
Just press the key a few times until the measurement level is reached again.
pas
paspas
pas
Password - Enter the correct password to unlock write operations for the
parameters in the following levels.
[Al
[Al[Al
[Al
Calibration low - Offset value of the input. It adjusts the lower
measurement range of the sensor.
[Ak
[Ak[Ak
[Ak
Calibration High - Gain calibration. It adjusts the upper measurement
range of the sensor.
[JL
[JL[JL
[JL
Cold Junction Offset calibration - This parameter is available only for
thermocouple.
FA(
FA(FA(
FA(
Factory Calibration - Restores factory calibration parameters. Change
from 0 to 1 to restore the calibration parameters with factory values.
Prt
PrtPrt
Prt
Protection - Defines the levels of parameters that will be password
protected. See "Configuration Protection" for details.
Pa(
Pa(Pa(
Pa(
Password Change - Allows changing the current password to a new one.
Values from 1 to 999 are allowed.
Sn2
Sn2Sn2
Sn2
Serial number - First part of the electronic serial number of the instrument.
This is a read only parameter.
sn1
sn1sn1
sn1
Serial number - Second part of the electronic serial number of the
instrument. This is a read only parameter.
sn0
sn0sn0
sn0
Serial number - Third part of the electronic serial number of the instrument.
This is a read only parameter.
WORKING WITH THE RHT CONTROLLER
Multiple output controllers are suited for controlling multiple stage systems.
Other applications require OUTPUT 1 to be the control output and OUTPUT 2 to be the alarm.
There are eight distinct alarm functions implemented in OUTPUT 2, selected by the parameter
Ac2
Ac2Ac2
Ac2, described below:
2
22
2 - Low alarm OUTPUT 2 is turned on when the selected variable, as assigned for
OUTPUT 2 in the (nt
(nt(nt
(nt parameter, falls below the SP2
SP2 SP2
SP2 value.
3
33
3 - High alarm OUTPUT 2 is turned on when the selected variable exceeds the
value programmed in SP2
SP2SP2
SP2.
4
44
4 - Inside range alarm OUTPUT 2 is turned on when the selected variable is within
the range defined by:
(SP1
SP1SP1
SP1 SP2
SP2 SP2
SP2) and (SP1
SP1SP1
SP1 + SP2
SP2 SP2
SP2)
5
55
5 - Outside range alarm: OUTPUT 2 is turned on when the selected variable falls
outside the range defined by:
(SP1
SP1SP1
SP1 SP2
SP2 SP2
SP2) and (SP1
SP1SP1
SP1 + SP2
SP2 SP2
SP2)
Functions 6
66
6, 7
77
7, 8
88
8 e 9
99
9 are identical to the above ones except that they incorporate the Initial
Blocking feature, which inhibits the output if an alarm condition is present at start-up. The
alarm will be unblocked after the process reaches a non-alarm condition for the first time.
In a multiple stage application, SP1
SP1SP1
SP1 and SP2
SP2SP2
SP2 are configured to operate at different settings,
creating a progressive sequence for turning on the outputs (compressors or resistances) in
response to a system’s demand. The output delays for turning on the compressors (dL1
dL1dL1
dL1 and
dL2
dL2dL2
dL2) cause the outputs to be turned on one by one, minimizing energy demand.
Another usage for multiple output controllers is in systems that require both direct and reverse
actions (for cooling and heating, simultaneously, for instance). In these applications, one
output is configured as reverse action and the other as direct action. The output status leds
P1 and P2 in the instrument panel signal the current action being performed.
CONFIGURATION PROTECTION
A protection system to avoid unwanted changes to the controller parameters is implemented.
The level of protection can be selected from partial to full. The following parameters are part
of the protection system:
Pas
PasPas
Pas When this parameter is presented, the correct password should be entered to allow
changes of parameters in the following levels.
Prt
PrtPrt
Prt Defines the level of parameters that will be password protected:
1 - Only calibration level is protected (factory configuration);
2 - Calibration and Configuration levels are protected;
3 - All levels are protected - calibration, Configuration and setpoints.
PA(
PA(PA(
PA( Parameter for definition of a new password. Since it is located in the calibration level,
can only be changed by a user that knows the current password. Valid passwords are
in the range 1 to 999.
CONFIGURATION PROTECTION USAGE
The PAS
PASPAS
PAS parameter is displayed before entering a protected level. If the correct password is
entered, parameters in all following levels can be changed. If wrong or no password is
entered, parameters in the following levels will be read only.
Important notes:
1- After five consecutive attempts to enter a wrong password, new tentative will be blocked for
the next 10 minutes. If the current valid password is unknown, the master password can be
used only to define a new password for the controller.
2 - The factory default password is 111.
MASTER PASSWORD
The master password allows user to define a new password for the controller, even if the
current password is unknown. The master password is based in the serial number of the
controller, and calculated as following:
[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ]
for example the master password for the device with serial number 987123465 is: 1 9 3 6
as follows: 1 + sn2
sn2sn2
sn2= 987; sn1
sn1sn1
sn1= 123; sn0
sn0sn0
sn0= 465 = 1 + 9 + 3 + 6
How to use the master password:
1- Enter the master password value at PaS
PaSPaS
PaS
prompt.
2- Go to PA(
PA(PA(
PA( parameter and enter the new password, which must not be zero (0).
3- Now you can use this new password to access all controller parameters with modify
rights.
ERROR MESSAGES
Sensor measurement errors force the controller outputs to be turned off. The cause for these
errors may have origin in a bad connection, sensor defect (cable or element) or system
temperature outside the sensor working range. The display signs related to measurement
errors are shown below:
Overflow
Underflow
Sensor error
Page view 1
1 2