TEMPERATURE AND HUMIDITY
CONTROLLER
N322RHT
OPERATING MANUAL - V1.7x A
Man 5001234
SPECIFICATIONS
INPUT SENSOR:
Humidity measurement: Accuracy: Refer to Figure 01;
Stability: < 1 %RH / year;
Range: 0 and 100 % RH
Linearity error: << 1 % RH;
Long term Stability: < 1 % RH
Response time: 4 seconds in the range from 10 to 90 %,
with slow moving air. Outside this range, up to 48 horas.
Temperature measurement: Accuracy: Refer to Figure 1;
Repeatability: ±0.1 °C;
Range: -40 and 120 °C (-3.8 to 211.8 °F)
Response time: up to 30 seconds in slow moving air.
WARM-UP: 15 minutes
MEASUREMENT RESOLUTION:
Temperature: 0.1º...........................................for indications between –19.9º and 119,9º
.................................................................................................... elsewhere
RH: ...............................................................................................................................................1%
OUTPUT1:.............................. Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A Resistive)
OUTPUT2:.......................................................................................Relay: 3A / 250 Vac, SPST
POWER SUPPLY: .................................100~240 Vac (± 10 %) or 24 Vdc/ac (12~30 Vdc/ac)
............................................................Mains frequency: 50~60 Hz. Power consumption: 5 VA
Caution: check the power supply specification before energizing the controller.
DIMENSIONS:..........................................................Width x Height x Depth: 74 x 32 x 75 mm
PANEL CUT-OUT: ..................................................................................................70 x 29 mm
WEIGHT: ...........................................................................................................................100 g
ENVIRONMENT:......................................... Operating temperature: 0 to 40 °C (32 to 122 °F)
......................................................................Storage temperature: -20 to 60 °C (-4 to 140 °F)
.......................................................................... Relative humidity: 20 to 85 % non condensing
CASE:...............................Polycarbonate UL94 V-2; Protection: Front panel: IP65, Box: IP42
SUITABLE WIRING: ............................................................................................Up to 4.0 mm²
RS-485 digital communication; RTU MODBUS protocol (optional)
Serial interface not isolated from input circuitry.
Serial interface isolated from input circuitry, except in 24 V powered model.
Relative Humidity Accuracy at 25°C
Temperature Accuracy
Sensor Operating Conditions
Figure 01- RH and Temperature accuracies.
The 322RHT is a digital controller for relative humidity and temperature. Its 2 relay outputs
can be configured independently as control or alarm, either for temperature or relative
humidity. The RHT probe (3 m length) is provided along with the instrument.
The features of a particular model (mains supply, digital communication, etc) are identified by
the label placed on the controller body.
ELECTRICAL WIRING
It is important to follow the recommendations below:
Signal wires should be installed in grounded conduits and away from power or contactor
wires.
The instrument should have its own power supply wires that should not be shared with
electrical motors, coils, contactors, etc.
Installing RC filters (47 R and 100 nF, series combination) is strongly recommended at
contactor coils or any other inductors.
System failure should always be taken into account when designing a control panel to
avoid irreversible damage to equipment or people.
Figure 1 below shows the controller connections to sensor, mains and outputs.
Figure 02 – N322RHT terminals
OPERATION
The controller requires the internal parameters to be configured according to the intended use
for the instrument. The parameters are organized in 4 groups or levels:
Level Function
0 Measurement
1 Setpoint Adjustment
2 Configuration
3 Calibration
Upon power-up, the N322RHT display shows for 1 second its firmware version. This
information is useful when consulting the factory.
Then, the measured input variable is shown on the display. This is the parameter level 0
(measurement level).
To access level 1, press for 1 second until the SP
SPSP
SP1
11
1” message shows up. Pressing
again, the “SP2
SP2SP2
SP2” parameter is presented. To go back to level 0, press once more.
To access level 2 of paramenters, press for 2 seconds until the RK
RKRK
RKT
TT
T message is
shown. Release the key to remain in this level. Each new pressing on the key will
advance to the next parameter in the level. At the end of the level, the controller returns to the
first level (0). Use the and keys to alter a parameter value.
Notes: 1 A parameter configuration is saved when the
key is pressed to advance to
the next parameter in the cycle. The configuration is stored in a non-volatile
memory, retaining its value when the instrument is de-energized.
2 If no keyboard activity is detected for over 20 seconds, the controller saves the
current parameter value and returns to the measurement level.
Level 1 –Setpoint Adjustment
In this level only the Setpoint (SP1
SP1 SP1
SP1 and SP2
SP2SP2
SP2) parameters are available, alternating the
names with their respective values. Adjust the desired value for each setpoint clicking on the
and
keys.
SP1
SP1SP1
SP1
Set Point 1
Set Point adjustment for control OUTPUT 1. SP1
SP1SP1
SP1 value is limited to the
values programmed in SPL
SPLSPL
SPL and SPk
SPk SPk
SPk in the programming level (Parameter
configuration, level 2).
SP2
SP2SP2
SP2
Set Point 2
Set Point adjustment for control OUTPUT 2. SP2
SP2SP2
SP2 value is limited to the
values programmed in SPL
SPLSPL
SPL and SPk
SPk SPk
SPk
Level 2 – Configuration - Parameters configuration Level
Contains the configuration parameters to be defined by the user, according to the system’s
requirements. Use and keys to set the value. The display alternates the parameter
name and respective value.
rkt
rktrkt
rkt
RH - Temp
Defines how the variables, relative humidity and temperature, will be
displayed:
0
00
0 Relative Humidity
1
11
1 Temperature
2
22
2 Toggles the indication every 2 seconds.
3
33
3 Toggles the indication every 3 seconds.
4
44
4 Toggles the indication every 4 seconds.
5
55
5 Toggles the indication every 5 seconds.
For options 0
00
0 and 1
11
1, a fast click on the
key forces the other variable to
be displayed for 10 seconds.
Unt
UntUnt
Unt
Temperature Unit - Selects display indication for degrees Celsius or
Fahrenheit.
0
00
0 - Temperature Celsius
1
11
1 - Temperature in degrees Fahrenheit
0fk
0fk0fk
0fk
RH Offset - Offset value to be added to the displayed relative humidity to
compensate for sensor mismatches (when replacing a sensor, for instance).
Adjustment range: between –10.0 and 10.0 % of RH. Default value: 0.0
0ft
0ft0ft
0ft
Temperature Offset - Offset value to be added to the measured
temperature to compensate for sensor mismatches. Adjustment range:
between –10.0 and 10.0 % of RH. Default value: 0.0
Sl1
Sl1Sl1
Sl1
Lower limit value for SP1
SP1SP1
SP1 (minimum value with which SP1
SP1 SP1
SP1 can be
configured). S
S S
Sl
ll
l1
1 1
1 must be programmed with a lower value than sK1
sK1sK1
sK1.
Sk1
Sk1Sk1
Sk1
Upper limit for Sp1
Sp1Sp1
Sp1 (maximum allowed value for Sp1
Sp1Sp1
Sp1). sK1
sK1sK1
sK1 must be
programmed with a value lower than the one configured in sl1
sl1sl1
sl1.
Sl2
Sl2Sl2
Sl2
Lower limit value for SP2
SP2SP2
SP2 (minimum value with which SP2
SP2 SP2
SP2 can be
configured). Sl2
Sl2 Sl2
Sl2 must be programmed with a lower value than sK2
sK2sK2
sK2.
Sk2
Sk2Sk2
Sk2
Upper limit for Sp2
Sp2Sp2
Sp2 (maximum allowed value for Sp1
Sp1Sp1
Sp1). sK2
sK2 sK2
sK2 must be
programmed with a value lower than the one in sl1
sl1sl1
sl1.
ky1
ky1ky1
ky1
OUTPUT 1 Hysteresis: defines the differential range between the input
variable value at which the OUTPUT 1 is turned on and the value at which it
is turned off. In degrees.
ky2
ky2ky2
ky2
OUTPUT 2 Hysteresis: defines the differential range between the input
variable value at which the OUTPUT 2 is turned on and the value at which it
is turned off. In degrees.
Ac1
Ac1Ac1
Ac1
Control action for OUTPUT 1 :
0
00
0 Reverse: For heating or humidification. Outputs turn on when
variable is lower than SP (See (nt
(nt(nt
(nt parameter below).
1
11
1 Direct: For cooling or dehumidification. Output turns on when
variable is above SP.
2
22
2 Low (minimum value) alarm.
3
33
3 High (maximum value) alarm.
4
44
4 Low alarm with initial blocking.
5
55
5 High alarm with initial blocking
Page view 0
1 2

Summary of Contents

Page 1 - N322RHT

TEMPERATURE AND HUMIDITY CONTROLLER N322RHT OPERATING MANUAL - V1.7x A Man 5001234 SPECIFICATIONS INPUT SENSOR: Humidity measurement: Accuracy:

Page 2 - ERROR MESSAGES

Ac2Ac2Ac2Ac2 Action 2 - Control OUTPUT 2 action or Alarm functions: 0000 Reverse control action (heating or humidification). (See (nt(nt(n

Comments to this Manuals

No comments